A case study on fault detection in power transformers using dissolved gas analysis and electrical test methods

Main Article Content

Koroglu S.

Abstract

This paper presents methodologies for power transformer fault diagnosis using dissolved gas analysis and electrical test methods. These methods are widely used in determination of inception faults of power transformers. Dissolved gas analysis test provides fault diagnosis of power transformers. On the other hand the electrical test methods are used for detection of root causes and fault locations and they provide more specific information about the faults. The aim of this work is to study the faults that are measured and recorded in Turkish Electricity Transmission Company (TEIAS) power systems. For this purpose, four specific cases are considered and analyzed with dissolved gas analysis and electrical testing methods. Three of these cases are defective situations and one case is a non-defective situation. These real cases of measurements have been analyzed with both methods in detail. Assessment results showed that a single method cannot yield accurate enough results in some specific fault conditions. Therefore it was concluded that cooperation of both methods in the assessment of fault condition gives more trustworthy results. 